| Display |
PV display |
11-segment Backlight LCD Red/Green/Orange, Character size, 12.0 x 5.4mm (H x W) |
| SV display |
11-segment Backlight LCD Green, Character size, 6.0 x 3.5mm (H x W) |
| MEMO display |
11-segment Backlight LCD Green, Character size, 4.8 x 2.8mm (H x W) |
| Indicators |
Backlight Orange |
| Input |
Thermocouple |
K, J, R, S, B, E, T, N, PL-II, C (W/Re5-26) External resistance: 100Ω or less(However, for B input: 40Ω or less) |
| RTD |
Pt100, JPt100 3-wire system
(Allowable input lead wire resistance per wire: 10Ω or less) |
| DC current |
0 to 20mA DC,
4 to 20mA DC |
Input impedence: 50Ω
(Connect shunt resistor 50Ω between input terminals)
Allowable input current: 50mA DC or less
(When shunt resistor 50Ω is used) |
| DC voltage |
0 to 1V DC |
Input impedence: 1MΩ or greater
Allowable input voltage: 5V DC or less
Allowable signal source resistance: 2kΩ or less |
0 to 5V DC,
1 to 5V DC,
0 to 10V DC |
Input impedence: 100kΩ or greater
Allowable input voltage: 15V DC or less
Allowable signal source resistance: 100Ω or less |
Accuracy
(Setting - Indicating)
|
Thermocouple |
Within +/-0.2% of each input span +/-1 digit or +/-2°C (4°F), whichever is greater
However, R or S input 0 to 200°C (0 to 400°F): Within +/-6°C (12°F)
B input 0 to 300°C (0 to 600°F): Accuracy is not guaranteed
K, J, E, T and N input less than 0°C (32°F): Within +/-0.4% of input span +/-1 digit |
| RTD |
Within +/-0.1% of each input span +/-1 digit or +/-1°C (2°F), whichever is greater |
DC current and
DC voltage |
Within +/-0.2% of each input span +/-1 digit |
Input Sampling
Period |
0.25 seconds |
Control Output
(OUT 1) |
Relay contact |
1a, control capacity: 3A 250V AC (Resistive load), 1A 250V AC (Inductive load cos φ=0.4). Electric life: 100,000 times |
| Non-contact voltage |
12V DC +/-15% Max. 40 mA (short-circuit protected) |
| DC current |
4 to 20mA DC Load resistance: Max. 550Ω |
| Control Action |
Actions mentioned below can be selected by keypad (Factory default set as PID) |
| PID (with auto-tuning function), PI, PD (with auto-reset function), P (with auto-reset function), ON/OFF |
| OUT1 proportional band (P) |
0 to 1000°C (0 to 2000°F), 0.0 to 1000.0°C (°F), or 0.0 to 100.0%
(ON/OFF action when set to 0 or 0.0) |
| Integral time (I) |
0 to 1000 seconds (OFF when set to 0) |
| Derivative time (D) |
0 to 300 seconds (OFF when set to 0) |
| OUT1 ON/OFF action |
When set the proportional band to 0 or 0.0 |
| OUT1 Proportional cycle |
1 to 120 seconds (DC current output type is not available) |
| ARW |
0 to 100% |
| OUT1 ON/OFF action hysteresis |
0.1 to 100.0°C (°F) or 1 to 1000 |
| OUT1 high limit setting |
0 to 100% (DC current: -5 to 105%) |
| OUT1 low limit setting |
0 to 100% (DC current: -5 to 105%) |
| Alarm 1 Output |
Alarm types can be selected by keypad (Default: No alarm action) |
| • No alarm action |
| • High limit alarm |
(Deviation setting) |
Setting Range: -(Input span) to Input span |
| • Low limit alarm |
(Deviation setting) |
Setting Range: -(Input span) to Input span |
| • High/Low limits alarm |
(Deviation setting) |
Setting Range: 0 to Input span |
| • High/Low limit range alarm |
(Deviation setting) |
Setting Range: 0 to Input span |
| • Process high alarm |
|
Setting Range: Input range low limit value to Input range high limit value |
| • Process low alarm |
|
Setting Range: Input range low limit value to Input range high limit value |
| • High limit alarm with standby |
(Deviation setting) |
Setting Range: -(Input span) to Input span |
| • Low limit alarm with standby |
(Deviation setting) |
Setting Range: -(Input span) to Input span |
| • High/Low limits alarm with standby |
(Deviation setting) |
Setting Range: 0 to Input span |
| When input is DC current or DC voltage, the input span is the same as the scaling span |
| When input is DC current or DC voltage, the input range low (or high) limit value is the same as the scaling low (or high) limit value |
| • Setting accuracy |
The same as the indicating accuracy |
| • Action |
ON/OFF action |
| • Hysteresis |
0.1 to 100.0°C (°F) or 1 to 1000 |
| • Output |
Relay contact 1a, Control capacity: 3A 250V AC (Resistive load), 1A 250V AC (Inductive load cos φ=0.4), Electric life: 100,000 times |
| Mounting Method |
Mounting frame (Mountable control panel thickness: Within 1 to 5mm) |
| Setting Method |
Sheet key input |
| Insulation Resistance |
10MΩ or more, at 500V DV |
| Dielectric Strength |
Between Input terminal-Power terminal, Between Output terminal-Power terminal ---- 1.5kV AC for 1 minute |
| Material - Color |
Material: Flame resistant resin |
Color: Black |
| Supply Voltage |
100 to 240V AC 50/60Hz, 24V AC/DC 50/60Hz
Allowable voltage fluctuation: 85 to 264V AC, 20 to 28 AC/DC, Power consumption: Approximately 8VA |
| Environment |
Ambient temperature: 0 to 50°C |
Ambient humidity: 35 to 85% RH (No condensation) |
| External Dimension |
W48 x H48 x D62mm (Depth of control panel interior when gasket is used: 54.5mm) |
| Weight |
Approximately 200g |
| Attached Functions |
Power failure countermeasure, Self-diagnosis, Automatic cold junction temperature compensation (only for thermocouple), Burnout, Input abnormality indication, Indication range, Control range, Warm-up indication, Auto/Manual control switching, Console communication |
Accessories
Included |
Mounting frame 1 piece, Gasket (Front mounted to the ACS-13A) 1 piece, Instruction Manual (A3 unfolded, Eng/Jap) 1 copy |
| CT (Current transformer): |
CTL-6S: 1 piece [W (20A) option] |
CTL-12-S36-10L1: 1 piece [W (50A) option] |
| |
CTL-6S: 2 pieces [W (20A) option] |
CTL-12-S36-10L1: 2 pieces [W (50A) option] |
| Accessories Sold Separately |
Terminal cover, 50Ω Shunt resistor (DC current input), USB communication cable CMA to which the console software SWS-ACS01M is attached |
| |
|
|
|
|
| > To Top |
|
|
|
|
| |
|
|
|
|
| Options |
* Please specify options according to user’s needs. When ordering, specify an option code to be applied. |
| |
|
|
|
|
Alarm 2 Output
[A2] |
Alarm type, setting range and output type, etc. are the same as those of Alarm 1. See Alarm 1 output section
If this option is applied, Heating/Cooling control (D option) cannot be added.
This option and Heater burnout alarm (W, W3 option) utilize common output terminals. |
Heater Burnout Alarm
[W, W3]
(CT Included) |
Rating |
Single Phase 20A [W(20A)], Single phase 50A [W(50A)], 3-phase 20A [W3(20A)],
3-phase 50A [W3(50A)] - Must be specified |
| Setting Range |
Rated current 20A [W(20A), W3(20A)]: 0.0 to 20.0A
Rated current 50A [W(50A), W3(50A)]: 0.0 to 50.0A |
| Setting Accuracy |
Within +/-5% of the rated value |
| Action |
ON/OFF action |
| Output |
Relay contact 1a, Control capacity: 3A 250V AC (Resistive load), 1A 250V AC
(Inductive
loading cos φ=0.4), Electric life: 100,000 times |
| If this option is added, Heating/Cooling control (D option) cannot be added |
Heating/Cooling
Control
[D☐] |
Heating control action: The same as the control output (OUT1)
Cooling control action |
| OUT2 proportional band (P) |
0.0 to 10.0 times the control output (OUT1) proportional band (ON/OFF action when set to 0.0) |
| OUT2 integral time (I) |
The same as that of the control output (OUT1) |
| OUT2 derivative time (D) |
The same as that of the control output (OUT1) |
| OUT2 proportional cycle |
1 to 120 seconds |
| Overlap/Dead band |
Thermocouple and RTD: -100.0 to 100.0°C (°F)
DC current and DC voltage: -1000 to 1000 (Decimal point follows this selection) |
| OUT2 hysteresis |
Thermocouple and RTD: 0.1 to 100.0°C (°F) |
| OUT2 action mode |
One cooling action can be selected from Air cooling (linear characteristic), Oil cooling
(1.5th power of the linear characteristic) and Water cooling (2nd power of the linear
characteristic) by keypad |
| Output |
Relay contact 1a, Control capacity: 3A 250V AC (Resistive load), 1A 250V AC (Inductive
load cos φ=0.4), Electric life: 100,000 times
Non-contact voltage 12V DC +/-15% Max. 40mA DC (short circuit protected) |
| If this option added, Alarm 2 (A2 option) and Heater burnout alarm (W, W3 option) cannot be added |
Serial Communication
[C5] |
Various operations such as reading and setting of various sets of values, reading of PV and action status and function change can be performed from the external PC. |
| Communication interface |
EIA RS-485 |
| Communication system |
Half-duplex communication start-stop synchronous |
| Communication speed |
2400/4800/9600/19200bps Selectable by key operation |
| Data bit/Parity |
Data bit: 7 or 8, Parity: Even/Odd/No parity (Can be selected by keypad) |
| Stop bit |
1 or 2 (Can be selected by keypad) |
| Communication protocol |
Shinko/Modbus RTU/Modbus ASCII (Can be selected by keypad) |
| Number of connectable units |
Max 31 units per host computer |
| Communication error detection |
Parity, checksum, LRC (Modbus ASCII), CRC-16 (Modbus RTU) |
| Data format |
| Communication Protocol |
Shinko Protocol |
Modbus ASCII |
Modbus RTU |
| Start bit |
1 |
1 |
1 |
| Data bit |
7 |
7 or 8 |
8 |
| Parity |
Yes (Even) |
Yes (Even, Odd) |
Yes (Even, Odd) |
| |
No Parity |
No Parity |
| Stop bit |
1 |
1 or 2 |
1 or 2 |
|
| If this option is added, Set value memory number external selection (SM Option) cannot be added |
| Set Value Memory
External Selection
[SM] |
SV1, SV2, SV3 or SV4 can be selected by the external contact.
The MEMO display indicates the selected memory number.
Contact input terminals DI2 can be used for “Set value memory external selection” or for ‘OUT/OFF external selection” during
the “Contact input function selection” of the Setup mode.
If Auto/Manual control function is selected during “OUT/OFF key function selection” in the Setup mode, externally
Auto/Manual control can be switched.
Circuit current when closed: Approximately 6mA
If this option is added, Serial communication (C5 option) cannot be added.
|
Terminal Cover
[TC] |
Electric shock protection terminal cover
Be sure to use this terminal cover by adding this option if operator may touch the back of the controller while running the
controller. |
 |
 |
 |
 |
 |